Capsule RTDs Page

  
Moderate, High and Full Temperature Specifications
Temperature Range Moderate (M) Range RTDs High (H) Range RTDs Full (F) Range RTDs
Temperature -50 to 250 °C (-58 to 482 °F) -50 to 500 °C (-58 to 932 °F) -200 to 500 °C (-328 to 932 °F)
Element Resistance 100 Ohms at 0 °C with tolerances of : 100 Ohms at 0 °C with tolerances of : 100 Ohms at 0 °C with tolerances of :
Class A +/-.06% @ 0°C Class A +/-.06% @ 0°C Class A +/-.06% @ 0°C
Class B +/-.12% @ 0°C (DIN to. Only over -50 to 400 °C) Class B +/-.12% @ 0°C
Class C +/-.5% @ 0°C Class B +/-.12% @ 0°C  
Temperature Coefficient .0038500 Nominal Temperature Coefficient .0038500 Nominal Temperature Coefficient .0038500 Nominal Temperature Coefficient
Class A: Change in T = +/-(.15°C + 002|t|) Class A: Change in T = +/-(.15°C + 002|t|) Class A: Change in T = +/-(.15°C + 002|t|)
Class B: Change in T = +/-(.30°C + 005|t|) Class B: Change in T = +/-(.30°C + 005|t|) Class B: Change in T = +/-(.30°C + 005|t|)
Class A: Change in T = +/-(1.3°C + 005|t|) Class A: Change in T = +/-(1.3°C + 005|t|) Class A: Change in T = +/-(1.3°C + 005|t|)
Time Constant Six seconds maximum for 63.2% response to change in temperature per ASTM E644 Four seconds maximum for 63.2% response to change in temperature per ASTM E644 Four seconds maximum for 63.2% response to change in temperature per ASTM E644
Repeatability Less than +/-.06% change in ice point resistance after 10 consecutive cycles between ice point and 250 °C Less than +/-.06% change in ice point resistance after 10 consecutive cycles between ice point and 500 °C Less than +/-.06% change in ice point resistance after 10 consecutive cycles between ice point and 500 °C
Long Term Stability Less than +/- .02% ice point resistance shift after 1000 hours at 250 °C Less than +/- .02% ice point resistance shift after 1000 hours at 500 °C Less than +/- .02% ice point resistance shift after 1000 hours at 500 °C
Self Heating 10 mW/°C in water moving at 3 feet/sec. 10 mW/°C in water moving at 3 feet/sec. 30 mW/°C in water moving at 3 feet/sec.
Hysteresis +/-.15% of Span Temperature +/-.15% of Span Temperature .1% of Span Temperature

   Class 100 General Purpose
Configure
   To detect temperatures in air, liquids, gases, and solids in a variety of process control applications.
   Class 101 Adjustable Compression Fitting
Configure
   To detect temperatures in air, liquids, gases, and solids in a variety of process control applications.
   Class 102 Plug and Jack Connector
Configure
   To detect temperatures in air, liquids, gases and solids in a variety of process control applications.
   Class 103 Transition and Strain
Configure
   To detect temperatures in air, liquids, gases and solids in a variety of process control applications.
   Class 104 Cut-to-Length
Configure
   To detect temperature in air, liquids, gases, and solids in a variety of process control applications.
   Class 105 Cut-to-Length, Adjustable Compression Fitting
Configure
   To detect temperatures in air, liquids, gases and solids in a variety of process control applications.