• View products by industry:

Capsule Thermocouples Page

  
H Style Mineral Insulated Thermocouple Specifications
Temperature Limits
Sheath OD AWG Type T Type J Type E Type K
1/8" 22 -200 to 315 °C 0 to 520 °C -200 to 650 °C -200 to 1070 °C
3/16" 19 -200 to 370 °C 0 to 620 °C -200 to 730 °C -200 to 1150 °C
1/4" 16 -200 to 370 °C 0 to 720 °C -200 to 820 °C -200 to 1150 °C
Color Code Red / Blue Red / White Red / Purple Red / Yellow
           
Accuracy
Thermocouple Type Temperature Range Standard Limits of Error Special Limits of Error
T -200 to 0°C +/-1°C or 1.5% Not ASTM Defined
0 to 350 °C +/-1°C or 0.75% +/-0.5°C or 0.4%
J 0 to 750 °C +/-2.2°C or 0.75% +/-1.1°C or 0.4%
E -200 to 0°C +/-1.7°C or 1% Not ASTM Defined
0 to 900 °C +/-1.7°C or 0.5% +/-1°C or 0.4%
K -200 to 0°C +/-2.2°C or 2% Not ASTM Defined
0 to 1250 °C +/-2.2°C or 0.75% +/-1.1°C or 0.4%

   Class 200 General Purpose
Configure
   To detect temperatures in air, liquids, gases and solids in a variety of process control applications
   Class 201 Adjustable Compression Fitting
Configure
   To detect temperatures in air, liquids, gases and solids in a variety of process control applications
   Class 202 Plug and Jack Connector
Configure
   To detect temperatures in air, liquid, gases, and solids in a variety of process control applications.
   Class 203 Transition and Strain Releif
Configure
   To detect temperatures in air, liquids, gases, and solids in a variety of process control applications.