Point Sensing RTDs Page

  
HVAC RTDs - Point Sensing
Temperature Limits Moderate (M) Range RTDs
-50 to 250 °C (-58 to 482 °F)
Element Resistance 100 Ohms at 0 °C with tolerances of :
Class A +/-.06% @ 0°C
Class B +/-.12% @ 0°C
Class C +/-.5% @ 0°C
Temperature Coefficient .0038500 Nominal Temperature Coefficient
Class A: Change in T = +/-(.15°C + 002|t|)
Class B: Change in T = +/-(.30°C + 005|t|)
Class A: Change in T = +/-(1.3°C + 005|t|)
Time Constant Six seconds maximum for 63.2% response to change in temperature per ASTM E644
Repeatability Less than +/-.06% change in ice point resistance after 10 consecutive cycles between ice point and 250 °C
Long Term Stability Less than +/- .02% ice point resistance shift after 1000 hours at 250 °C
Self Heating 10 mW/°C in water moving at 3 feet/sec.
Hysteresis +/-.15% of Span Temperature

   Class 500 Rigid General Purpose