• View products by industry:

Transmitters

  
RTD and Thermocouple Temperature Transmitters and Specifications
Class 675 676 677 678 679 680
Description Analog Transmitter HART Transmitter Analog Transmitter Digital TC Transmitter Analog DIN Rail Transmitter Indicator
Mounting Style DIN Puck DIN Puck DIN Puck DIN Puck DIN Rail Transmitter Mounted
Sensor Input SI 19 SI 32 SI 24 SI 23 SI 19 DI
RTD Yes, 3 Wire Yes, 2, 3, or 4 wire Yes, 3 Wire No Yes, 3 Wire Yes, 4-20mA
PT100, .00385 TC. PT100, .00385 TC. PT100, .00385 TC. PT100, .00385 TC.
TC Yes, Types T, J, K, S Yes, Types J, K, N, T, E  No Yes, Types J, K, N, T, E, L, Yes, Types T, J, K, S Yes, 4-20mA
L,U,R ,S, B U, R, S, B, W3, W5
Sensor Output            
Nominal 4-20 mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA 5 Digit Display
Maximum 23.5 mA 23 mA 23 mA 21 mA 23.5 mA -1999 to 9999
Minimum 3 mA 3.8 mA 3 mA 3.6 mA 3 mA for 4-20mA Input
Temperature Ranges (RTD)            
Setup Factory Set Factory Set or with Software Factory Set or with Software Factory Set Factory Set Simple Pushbutton
Field Changes Adjustable Pots Hart Compatible With Software No Adjustable Pots Simple Pushbutton
Range -200 to 850°C -200 to 850ºC -200 to 850ºC -200 to 850ºC -200 to 850°C -1999 to 9999 for 4-20mA
Minimum Span 50°C 10ºC RTD, 50ºC TC 50ºC 50ºC 50°C See Transmitter
Accuracy (RTD) ± 0.5% of Span + 0.08ºC + 0.2% +/- 0.05% ± 0.5% of Span +/- 0.5% of Span
Sensor Failure Indication Up or Downscale for Up or Downscale for Up or Downscale for Up or Downscale for Up or Downscale for See Transmitter
Burnout & Short Circuit Burnout & Short Circuit Burnout & Short Circuit Burnout & Short Circuit Burnout & Short Circuit
EMI and RFI Protection CE conformity per EN CE conformity per EN CE conformity per EN CE conformity per EN CE conformity per EN Less than or equal to
50082-2 (March 95)  50082-2 (March 95)  50082-2 (March 95)  50082-2 (March 95)  50082-2 (March 95) 0.5% Typical
Ratings CE CE, FM, CSA, CENELEC, CE, FM, CSA, UL, CENELEC, CE CE EN 50 081 (1993)
EN 50 082 (1995)
Intrinsically Safe Intrinsically Safe IEC 61326-1 (1998)
Supply Voltage 10V to 30V 12V to 42V 10V to 30V 9V to 36V 10V to 30V Loop Powered
Matched Transmitter/Sensor 100 Ohm, .00385 Available 100 Ohm, .00385 Available 100 Ohm, .00385 Available Not Available 100 Ohm, .00385 Available  
Not Applicable
 

   Class 675 Analog
Configure
   Analog Transmitter for RTD or Thermocouple
   Class 676 Programmable
Configure
   Programmable Transmitter, software available or factory set. Available RTD and Thermocouple
   Class 677 Programmable Analog
Configure
   Available for RTD Only-range set at factory or, Transmitter Confguration Kit also available.
   Class 677CK Transmitter Configuration Kit
Configure
   For Class 677 Programmable Analog Transmitter
   Class 678 Digital Thermocouple
Configure
   Quick delivery for Thermocouples
   Class 679 Analog DIN Rail
Configure
   Analog DIN Rail Transmitter
   Class 680 Indicator with Optional Transmitter
Configure
   Explosion Proof Aluminum Head with Indicator and Optional Transmitter
   Class 688 Digital Panel
Configure
   Digital Panel Meter
   Class 689 Scanner
Configure
   8 Channel Scanner